A.O. Smith COF-199 THRU 700A Specifications Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
5
The discharge opening of the relief valve should always be piped
to an open drain.
Choose the point of major hot water usage, fuel supply and chimney.
Try to make hot water and oil piping as short as possible.
Insulate hot and cold water piping where heat loss and
condensation may be a problem.
CLEARANCES
The heater has minimum clearances to combustible material, on a non-
combustible floor of: 6 inches (152 mm) from the sides and rear, 24
inches (610 mm) from the front, and 18 inches (457 mm) from the vent
connector. These clearances are, as shown in fig. 4A to prevent possible
fire hazard conditions.
At least 24" (610 mm) of top clearances are recommended for vertical
vent installation.
Allow sufficient room at rear of heater for servicing of T&P relief valve.
At least 24" (610 mm) should be provided at the front of the unit for
proper servicing.
Units which are to be installed on combustible flooring must be supported
by a full layer of hollow concrete blocks, fig. 4, from 8" (203 mm) to
12" (305 mm) thick and extending 12" (305 mm) minimum beyond the heater in
all directions. The concrete blocks must provide an unbroken concrete surface
under the heater, with the hollows running continuous and horizontally. A 3/
16" (4.8 mm) steel plate must cover the concrete blocks, see fig. 3.
PROPER INSTALLATION ON COMBUSTIBLE FLOORING
FIGURE 4
NOTE: If electrical conduits run under the floor of the proposed heater
location, insulate the floor as recommended above.
PROPER INSTALLATION CLEARANCES FOR TWO DIFFERENT
VENTING SYSTEMS
FIGURE 4A
* HOT WATER OUTLET LOCATION AT FRONT OF HEATER
FACTORY FURNISHED HEATER MANIFOLD KITS (OPTIONAL) ARE
DESIGNED FOR 10" (254 mm) SPACING BETWEEN SIDES OF
ADJACENT UNITS.
COMBUSTION AND VENTILATION AIR
GENERAL
The water heater area should have sufficient air for satisfactory
combustion of oil, and proper venting and of safe ambient temperature.
When a heater is installed in an area where exhaust or ventilating fans
may create unsatisfactory combustion or venting, approved provisions must
be made to overcome the problem, see NFPA Standard No. 31, Chapter 1.
CHEMICAL VAPOR CORROSION
Water heater corrosion and component failure can be caused by the
heating and breakdown of air borne chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioning
refrigerants, swimming pool chemicals, calcium and sodium chlorides,
waxes, and process chemicals are typical compounds which are
potentially corrosive. These materials are corrosive at very low
concentration levels with little or no odor to reveal their presence.
Products of this sort should not be stored near the heater. Also, air
which is brought in contact with the water heater should not contain any
of these chemicals. If necessary, uncontaminated air should be obtained
from remote or outside sources.
UNCONFINED SPACES (Building Construction)
NOTE: An uncontaminated space is defined as a space whose volume
is not less than 50 ft
3
per 1000 BTUH (4.83m
3
per kW)of total input
of all fuel burning appliances installed in that space. The unconfined
space may be thought of as extending to all areas which cannot
be separated by a door or door(s). All other spaces not fitting
this description, should be thought of as confined space.
1. In unconfined spaces in buildings of conventional frame, brick or
stone construction, infiltration will normally supply an adequate
amount of air for combustion and ventilation.
2. If the unconfined space is within a building of tight construction, eg.
weather stripping, heavy insulation, caulking, vapor barrier, ect., air
infiltration may be insufficient to support proper combustion and
ventilation, air shall be obtained from outdoors or from spaces freely
communicating with the outdoors.
Follow the instructions under Part 2 of Confined Spaces (Room
Construction)
CONFINED SPACES (Room Construction)
1. All air from inside building (conventionally constructed buildings only):
The confined space shall be provided with two permanent openings,
one within 12" (305 mm) of the ceiling and one within 12" (305 mm) of
the floor, fig. 5.
FIGURE 5
Each opening shall have a free area of not less than one square
inch per 1,000 Btu per hour (140 square inches per gallon of oil
consumed per hour) of the total input rating of all appliances in the
enclosure, freely communicating with the interior areas having in
turn adequate infiltration from the outside. In all cases, each
opening shall not have a free area of less than 100 square inches.
2. All Air From Outdoors: The confined space shall be provided with
two permanent openings, one in or within 12" of the top of the
enclosure and one in or within 12" of the bottom. The openings shall
communicate directly, or by means of ducts, with outdoors or such
spaces that freely communicate with outdoors.
If the appliance room is located against an outside wall and the air
openings communicate directly with the outdoors, each opening
shall have a free area of not less than one square inch per 4,000
Btu per hour (35 square inches per gallon of oil consumed per
hour) of the total input rating of all appliances in the enclosure.
Page view 4
1 2 3 4 5 6 7 8 9 10 ... 55 56

Comments to this Manuals

No comments