PRINTED 0313 213064-001MODELS HW-120M, 160M, 200M, 225M COMMERCIAL GAS COPPER HEAT EXCHANGER WATER HEATERBURKAY UP-FLOW MODELSIncluding Models with I
10INSTALLATION INSTRUCTIONSIMPORTANTStrict adherence to installation wiring diagrams shown in this manual is required to prevent constant pump operati
11CONFINED SPACEWhen drawing combustion and dilution air from inside a conventionallyconstructedbuildingtoaconnedspace,suchaspace shall be p
12Your local code authority may have other specic relief valverequirements not covered in this section.THE PURPOSE OF A RELIEF VALVE IS TO
13PIPING DIAGRAMS(USE THIS DIAGRAM FOR STRAIGHT RECOVERY SYSTEMS SUPPLYING HOT WATER AT ONE TEMPERATURE ONLY)FIGURE 7 DANGERTEMPERATURE SETTING SHOULD
14FIGURE 8 DANGERTEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 21. IF HIGHER P
15FIGURE 9 DANGERTEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 21. IF HIGHER
16GAS CONNECTIONS WARNINGTHE INLET GAS PRESSURE MUST NOT EXCEED THE VALUE SPECIFIED BY THE MANUFACTURER ON THE RATING PLATE (10.5” W.C. - NATURAL GAS,
17ELECTRICAL WIRING DIAGRAMS FOR THE HW-120M, 160M, 200M AND 225M WATER HEATERS I.I.D. SYSTEM (NATURAL)FIGURE 10A minimum gas supply pressure of
18ELECTRICAL WIRING DIAGRAMS FOR THE HW-120M, 160M, AND 200M WATER HEATERS I.I.D. SYSTEM (PROPANE)FIGURE 11
19OPERATIONIMPORTANTOnlyqualiedpersonnelshallperformtheinitialringoftheheater.At this time the user should not hesitate to ask the start
2GENERAL SAFETY
20OPERATING INSTRUCTIONS FOR I.I.D. MODELSTheI.I.D.modelshaveanautomaticintermittentsparkignitionsystem,gure3,mountedonthejacketatth
21 DANGERHOT WATER TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS RESULTINGINSERIOUSPERSONALINJURYAND/ORDE
22SERVICE INFORMATIONThe installer may be able to observe and correct certain problems which may arise when the unit is put into operation. HOWEVER,
23PILOT BURNER USED ON I.I.D. SYSTEMSFIGURE 14PROTECTOR SWITCH(COIL HIGH LIMIT - ALL HEATERS)Ifthe protector switch,g2,should shut offunit,
24PREVENTIVE MAINTENANCERECOMMENDED PROCEDURE FOR PERIODIC REMOVAL OF LIME DEPOSITS FROM COIL TYPE COMMERCIAL WATER HEATERS CAUTIONDO NOT USE A NYLON
25The usage of water softening equipment greatly reduces the hardness of the water. However, this equipment does not always remove all of the har
26CHART 1 - CER-TEMP 80 RECOVERY SYSTEM CHECKOUT PROCEDURE(USETHISCHECKOUTFORCER-TEMP80RECOVERYSYSTEMS)CHECKOUTThe checkout sequence should be
27 CHART 2S8600/S8610 (NATURAL GAS AND LP GAS)INTERMITTENT PILOT SYSTEM TROUBLESHOOTINGNO SPARK AT PILOT BURNERTurn gas supply off.Isvoltage(24Vac)
28CHART 2S8600/S8610 (NATURAL GAS AND LP GAS) INTERMITTENT PILOT SYSTEM TROUBLESHOOTINGEnsureallmanualshutoffvalvesarefullyopen;Allltersare
29CHART 2S8600/S8610 (NATURAL GAS AND LP GAS) INTERMITTENT PILOT SYSTEM TROUBLESHOOTINGPILOT BURNER LIGHTS BUT MAIN BURNER DOES NOT LIGHTDoesthepilo
3SAFE INSTALLATION, USE AND SERVICEYour safety and the safety of others is extremely important in the installation, use, and servicing of this water h
30CHART 3LED STATUS AND TROUBLE SHOOTINGThe following procedures are provided as a general guide. Any module should be replaced if it does not perform
31Green LEDFlash Code(X + Y)aIndicatesNext System ActionRecommendedService ActionOFF No “Call for Heat” not applicable noneFlash Fast Startup - Flame
32Green LEDFlash Code(X + Y)aIndicatesNext System ActionRecommendedService ActionOFF No “Call for Heat” not applicable noneFlash Fast Startup - Flame
33NOTES
34NOTES
35MODEL HW LIMITED WARRANTYA. O. Smith Corporation, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.1. If wit
36500 Tennessee Waltz ParkwayAshland City, TN 37015www.hotwater.com
4TABLE 2 - RECOVERY CAPACITIES ModelInputU.S. Gallons/Hrs. and Litres/Hr. at TEMPERATURE RISE INDICATEDT ° F 20 40 50 60 70 80BTUH KW T ° C 11.1 22.2
5FOREWORDThis design complies with the current edition of the ANSI Standard Z21.10.3 for gas water heaters Vol. III Storage Water Heaters with input r
6SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE TO THE WATER HEATER.Heater must be protected from
7AUTOMATIC GAS SHUTOFF CONTROLTheautomaticgasshutoffcontrol,g.1,isanautomaticsafetydevice which activates at a water temperature of approx
84. Discontinuesignitionsparkwhenpilotameisestablished.TheS8600 / S8610controlusedonpropanegasmodelsprovidessafetylockoutifpilot
9 CAUTIONAny part of the paddle must not touch the pipe or any restrictions inthepipe.Screwtheowswitchinpositionsotheatofthepaddleis